ARM3E Series electronic type adjustable type mccb 400V/690V 800 amp 3/4 Poles Built in LSIG Trip Unit
MCCB Highlights
Advantages for MCCB Electronic type
Welding process flow of hardware parts
1. Copper material-punching and forming-pickling-surface treatment/electroplating of copper parts-welding
2. Our after-sales rate of copper electroplating does not exceed 3 in 7 years
After degreasing agent, pickling, cleaning, silver plating (the printing plate is converted into silver molecules by electrolysis, and then adsorbed on the copper by electrodes), cleaning, drying, drying at 100 ℃ and other processes, the following parts are obtained
3. Our copper electroplating silver content is up to 99.9999999%.
4. Through 7.5% potassium sulfide experiment, the time can be as long as 15 minutes, it solves the defects of unstable welding and discoloration of copper parts in the same welding process. The function is to ensure that the electroplated coating does not blacken and discolor within the specified time
Main performance index of ARM3E series circuit breaker
Model | ARM3E-800 | ||||
Rated current In (A) | 630A、640A、660A、680A、700A、 720A、740A、760A、780A、800A | ||||
Rated current of frame size Inm (A) | 800A | ||||
Usage category | Category B | ||||
Rated ultimate short-circuit breaking capacity level | M | H | |||
Number of poles (P) | 3P | 3P | 4P | 4P | |
Rated working voltage Ue (V) | 400V | ||||
Rated ultimate short-circuit breaking capacity Icu (kA) | 75kA | 100KA |
|||
Rated service short-circuit breaking capacity Ics (kA) | 50kA | 65KA | |||
Rated short-time withstand current Icw (kA/1S) | 10KA/1s |
||||
Rated working voltage Ue (V) | 690V | ||||
Rated ultimate short-circuit breaking capacity Icu (kA) | 30KA | ||||
Rated service short-circuit breaking capacity Ics (kA) | 20KA | ||||
Rated insulation voltage Ui (V) | 1000V | ||||
Rated impulse withstand voltage Uimp (V) | 8kV | ||||
Mechanical life (time) | 2500 | ||||
Electrical life (time) | 500 | ||||
Arcing distance (mm) | ≯100 | ||||
W*L*H (mm) | 3P | 210.5*281.116 | |||
4P | 281*281.116 | ||||
package 3p | 260*310*175 | ||||
package 4p | 325*300*180 | ||||
weight 3P | 10267g | ||||
weight 4P | 13103g |
Overall and installation dimensions of circuit breaker
Circuit breaker 800 frame size installation safety interval
■ Front panel wiring (3P, 4P)
X-X, Y-Y are the center of three-pole circuit breaker
■ Rear panel wiring (3P, 4P)
X-X, Y-Y are the center of three-pole circuit breaker
■ Plug-in rear panel wiring (3P, 4P)
X-X, Y-Y are the centers of three-pole circuit breake