ARM3E Series electronic type adjustable type Molded Case Circuit Breaker 400V/690V 400A 3/4 poles Built in LSIG Trip Unit
MCCB Highlights
Advantages and highlights of welding process equipment for MCCB Electronic type hardware parts
1. Side heating resistance welding process: the silver spot welding transfers heat from copper heating to silver spot welding. The silver spot has no electrical corrosion damage, which does not cause the silver spot surface to fade and become soft. It retains the original state of the silver spot. The contact has no damage, and the welding consistency is good, which increases the mechanical life and electrical life of the contact point by 15%.
2. The infrared temperature control technology is used to precisely control the welding parameters, which ensures the welding quality and greatly improves the service life of the product by 50%.
Main performance index of ARM3E series circuit breaker
Model | ARM3E-400 | |||||
Rated current In (A) | 160A,180A,200A,225A, 250A,280A,315A, 350A,375A,400A |
|||||
Rated current of frame size Inm (A) | 400A | |||||
Usage category | Category B | |||||
Rated ultimate short-circuit breaking capacity level | L | M | H | |||
Number of poles (P) | 3P | 3P | 3P | 4P | 4P | |
Rated working voltage Ue (V) | 400V | |||||
Rated ultimate short-circuit breaking capacity Icu (kA) | 50kA | 65KA |
100KA | |||
Rated service short-circuit breaking capacity Ics (kA) | 50kA | 42KA | 65KA | |||
Rated short-time withstand current Icw (kA/1S) | 5KA/1s |
8KA/1s |
||||
Rated working voltage Ue (V) | 690V | |||||
Rated ultimate short-circuit breaking capacity Icu (kA) | 20KA | |||||
Rated service short-circuit breaking capacity Ics (kA) | 15KA | |||||
Rated insulation voltage Ui (V) | 1000V | |||||
Rated impulse withstand voltage Uimp (V) | 8kV | |||||
Mechanical life (time) | 4000 | |||||
Electrical life (time) | 1000 | |||||
Arcing distance (mm) | ≯100 | |||||
W*L*H (mm)
![]() |
3P | 150*258*111 | ||||
4P | 200*258*111 | |||||
package 3p | 198*277*177 | |||||
package 4p | 250*280*180 | |||||
weight 3P | 5712g | |||||
weight 4P | 7808g |
Overall and installation dimensions of circuit breaker
Circuit breaker 400 frame size installation safety interval
■ Front panel wiring (3P, 4P)
X-X, Y-Y are the center of three-pole circuit breaker
Model | C | D | ||
ARM3R-630(L/M/H) |
ARM3-400(C/L/M/H) |
ARXM3-400L/M/H |
40 | 59 |
ARM3L-400(L/M/H) |
ARM3ER-630(L/M/H) | ARM3E-400L/M/H |
26 | 49 |

■ Rear panel wiring (3P, 4P)
X-X, Y-Y are the center of three-pole circuit breaker

■ Plug-in rear panel wiring (3P, 4P)
X-X, Y-Y are the centers of three-pole circuit breake