Leave Your Message

Air circuit breaker ARW1-2000 ACB breaker drawer/fixed type 400VAC/690VAC 2000A 3 poles 4 poles

ARW1

Air circuit breaker ARW1-2000 ACB breaker drawer/fixed type 400VAC/690VAC 2000A 3 poles 4 poles

    ARW1 Highlights

    Several components work together in an ACB. One of the main features is a blast valve. When the arcing contacts separate and the arc forms, the blast valve opens arc chutes. Pressurized air pushes through the arc, disconnecting it from the contacts.
    The pressurized air pushes the arc towards arcing probes and rings. These are conductive elements that help to move the arc away from the contacts. As the arcing contacts get farther apart, the arcing probes and coils get closer together, allowing them to attract the arc.
    The arc is moved into the chutes toward an arcing electrode. Eventually, the arc is pushed through the chutes and stretched until it is completely eliminated.

    ARW1

    Main performance index of ARW1 series circuit breaker

    Model ARW1-2000
    Rated current In (A) 40℃ 630A, 800A, 1000A, 1250A, 1600A, 2000A
    Rated current of frame size Inm (A)
    2000A
    Usage category Category B
    Number of poles (P) 3P 4P
    Rated working voltage Ue (V) AC400V
    Rated ultimate short-circuit breaking capacity Icu (kA) 80KA
    Rated service short-circuit breaking capacity Ics (kA) 80KA
    Rated short-time withstand current Icw (kA/s) 65KA/s
    Rated working voltage Ue (V) AC690V
    Rated ultimate short-circuit breaking capacity Icu (kA) 65KA
    Rated service short-circuit breaking capacity Ics (kA) 65KA
    Rated short-time withstand current Icw (kA/s) 50KA/s
    Rated insulation voltage Ui (V) 1000V
    Rated impulse withstand voltage Uimp (V)
    12kv
    Arcing distance (mm) 0
    Installation method Draw-out type, fixed type
    Electromagnetic compatibility 
    (EMC)
    Environment A
    Isolation applicability Isolation
    W*L*H (mm)img9(1)u34 3P 410×432×400 370×402×310
    4P 505×460×575 466×402×310
    package 3p 505×460×575
    package 4p /
    Weight 3p 7200G 4500G
    Weight 4p 9000G 5400G

    Overall and installation dimensions of circuit breaker

    ARW1-2000 fixed circuit breaker overall and installation dimension


    2000285

    ARW1-2000 draw-out circuit breaker overall and installation dimension

    3000dyk

    Accessories of Air circuit breaker

    YANG8600-11ybw

    MCCB Production Line Real Showing

    Leave Your Message