ARM5 series thermal magnetic type double-breaker mccb 200ka icu=ics Thermal ajustable type mccb 400VAC/415VAC/550VAC/ 690VAC/800VAC400A 630A 3/4 Poles
MCCB Highlights
The reasonable structure design of moving and fixed contacts makes the short circuit peak value and energy of this series of products I²t much smaller than expected
Working principle: the current flows in from the fixed contact
1, flows out from the fixed contact
2, through the moving, fixed silver contact and the moving contact. The moving contact quickly disconnects under the action of strong electric repulsion force (Holm force and Lorentz force) to improve the breaking speed.
Air blowing design: when the short circuit large current occur in the circuit, the gas producing parts will generate other gas under the high temperature of the arc, the air pressure in the contact unit box increases rapidly, and a high-speed air flow can be formed through the air outlet of the arc extinguishing chamber, which can effectively extinguish the arc.
Main performance index of ARM5 series circuit breaker
Model | ARM5-630 | ||||||||||||
Rated current In (A) | 400A/500A/630A | ||||||||||||
Rated current of frame size Inm (A) | 630A | ||||||||||||
Usage category | Category A | ||||||||||||
Rated ultimate short-circuit breaking capacity level | L | M | H | ||||||||||
Number of poles (P) | 3P | 4P | 3P | 4P | 3P | 4P | |||||||
Rated working voltage Ue (V) | 400V/415V | ||||||||||||
Rated ultimate short-circuit breaking capacity Icu (kA) | 85kA | 150kA | 200kA | ||||||||||
Rated service short-circuit breaking capacity Ics (kA) | 85kA | 150kA | 200kA | ||||||||||
Rated working voltage Ue (V) | 550V/690V | ||||||||||||
Rated ultimate short-circuit breaking capacity Icu (kA) | 35kA | 50kA | 65kA | ||||||||||
Rated service short-circuit breaking capacity Ics (kA) | 35kA | 50kA | 65kA | ||||||||||
Rated insulation voltage Ui (V) | 1000V | ||||||||||||
Rated impulse withstand voltage Uimp (V) | 8kV | ||||||||||||
Mechanical life (time) | 7000 | ||||||||||||
Electrical life (time) 400ln |
1000 | ||||||||||||
Arcing distance (mm) | 0 | ||||||||||||
Release type | Thermomagnetic | ||||||||||||
W*L*H (mm) | W | 140 | 185 | 140 | 185 | 140 | 185 | ||||||
L | 123.5 | ||||||||||||
H | 123.5 | ||||||||||||
Overall and installation dimensions of circuit breaker
Circuit breaker 630 frame size installation safety interval
■ ARM5-630 front panel wiring (3P/4P)
X-X, Y-Y are the center of three-pole circuit breaker
Model | H | H1 | H0 |
B | C | D |
ARM5-630 | 123.5 | 167.1 | ||||
ARM5E-630 | 123.5 | 167.1 | ||||
ARM5EHU-630 | 123.5 | 167.1 |